Factory-direct transformer manufacturer · Xuzhou, China

IEC 60076 · IEEE C57.12 · 50 Hz and 60 Hz designs

Pad-Mounted Transformer Buying Guide

Pad-Mounted Transformer Buying Guide

Buying guide · Tianhua Transformer engineering team

Quick answer

Choose the kVA, primary and secondary voltage, loop or radial feed, fusing and switching, and fluid (mineral oil or FR3 natural ester). Tianhua makes tamper-resistant pad-mounted transformers to IEEE / ANSI C57.12: three-phase 45–5,000 kVA and single-phase up to 167 kVA, 2.4–34.5 kV primary, 120–600 V secondary, 60 or 50 Hz.

Pad-mounted transformers sit on a concrete pad inside a locked steel cabinet and feed underground cable networks for housing, commercial sites, campuses and solar plants.

Get a quote in 24 hoursDownload catalogue

Three-phase pad-mounted transformer built by Tianhua
Three-phase pad-mounted transformer built by Tianhua

At a glance

Three-phase45 kVA to 5,000 kVA
Single-phaseUp to 167 kVA
Primary2.4 kV to 34.5 kV
Secondary120 V to 600 V
FluidMineral oil (ONAN) or Envirotemp FR3 natural ester (KNAN)
FeedLoop feed or radial feed
StandardsIEEE / ANSI C57.12; 60 Hz or 50 Hz

1. Standard ratings and voltages

Values
Three-phase kVA45, 75, 112.5, 150, 225, 300, 500, 750, 1,000, 1,500, 2,000, 2,500, 3,000, 3,750, 5,000
Primary voltage2,400 / 4,160 / 4,800 V; 12,000–14,400 V; 20,780–26,400 V; 33,000 / 34,500 V
Secondary voltage208Y/120 V, 240 V, 416 V, 480Y/277 V, 600 V

2. Loop feed or radial feed?

Loop feedRadial feed
Primary bushingsTwo per phase (6 for three-phase)One per phase (3 for three-phase)
NetworkUnderground ring; the cable continues to the next unitEnd of a feeder line
BenefitA cable fault can be isolated and supply restored from the other sideSimpler and lower cost

3. Fusing and switching

  • bay-o-net expulsion fuses, usually in series with current-limiting fuses
  • two-position or four-position load-break switch (loop feed)
  • dead-front design with load-break elbows
  • options: surge arresters, tap changer, fault indicators

4. Mineral oil or FR3 natural ester?

Mineral oil is the standard choice. Envirotemp FR3 natural ester has a much higher fire point and is biodegradable, so it suits sites near buildings, in environmentally sensitive areas and where insurers ask for less-flammable fluid.

5. Options for special projects

  • step-up design for solar inverters
  • K-factor design for harmonic loads
  • electrostatic shield
  • stainless steel tank and cabinet for coastal sites
  • tamper-resistant cabinet with padlock provisions

6. Tests before shipment

Routine tests to IEEE C57.12.90: resistance, ratio, polarity and phase relation, losses and impedance, applied and induced voltage tests, and leak test. The test report is sent before shipment.

7. What to send for a quotation

  • rated power (kVA or MVA) and quantity
  • primary and secondary voltage, frequency (50 or 60 Hz) and vector group
  • standard: IEC 60076, IEEE / ANSI C57.12, GB or a utility specification
  • tap changer range and type
  • loss requirement or efficiency rule (or loss capitalisation values for TCO evaluation)
  • site conditions: indoor or outdoor, altitude, ambient temperature, corrosion class
  • destination port or site and preferred Incoterm
  • loop or radial feed
  • fusing, switch and fluid preference
  • utility specification, if any

Who makes these transformers

Transformer workshop at the Tianhua factory in Xuzhou, China

This guide is written by the engineering team of Jiangsu Tianhua Transformer Co., Ltd., a transformer manufacturer founded in 2013 in Xuzhou, Jiangsu, China. Every unit is designed, built and tested in our own 107,000 m² plant: core cutting, winding, drying, resin casting, tanks, radiators, assembly and testing. You deal directly with the factory engineers.

  • 500+ employees, including 7 senior engineers
  • ISO 9001 quality system; IEC, IEEE / ANSI and GB designs
  • SSZ11-40000/110 passed short-circuit and full type tests at a national test center
  • Exported to more than 30 countries and regions

About Tianhua · Factory and testing · Certificates · Projects

Frequently asked questions

Loop feed or radial feed: which do I need?

Loop feed has two primary bushings per phase so the cable ring can continue; use it on looped underground networks. Radial feed has one set and ends a feeder line.

Can you supply FR3 natural ester fluid?

Yes. Envirotemp FR3 (KNAN) is available for higher fire safety and biodegradability.

Do you make step-up pad-mounted transformers for solar?

Yes, step-up designs for inverter output are available. See our solar, wind and BESS transformer guide.

What is the difference between a pad-mounted transformer and a compact substation?

A pad-mounted transformer is a transformer in a cabinet with fused MV connections. A compact substation adds MV switchgear and an LV switchboard in a larger enclosure.

Do you make single-phase pad-mounted transformers?

Yes, single-phase units up to 167 kVA.

Can you make pad-mounted transformers for 50 Hz?

Yes, both 60 Hz and 50 Hz designs are available.

Request a pad-mounted transformer quotation

Send capacity, voltages, standard, quantity and destination. Our engineers reply with a datasheet and price within 24 hours.

Email sale@thatransformer.comWhatsAppCall Ivy Xiao