Factory-direct · S11 to S22 · 30 kVA to 31,500 kVA
Tianhua builds seven oil-immersed transformer series, from the standard S11 to the grade 1 energy-efficiency S22 and 35 kV power transformers. Compare the series below, then open any series for its full rating table.
Quick answer: all 10 kV series below are fully sealed, three-phase, 50 Hz oil-immersed distribution transformers for 6–10 kV to 0.4 kV. They differ mainly in core material and loss level. At 630 kVA, no-load loss drops from 810 W (S11-M) to 460 W (S22-M) and 320 W (SH15-M amorphous alloy).

Standard loss level, widely specified

30% lower no-load loss than S11-M at 630 kVA

3D wound triangle core

Amorphous alloy core, 60% lower no-load loss than S11-M

Energy efficiency grade 2 (GB 20052-2020)

Energy efficiency grade 1 (GB 20052-2020)

Power transformer, off-circuit or on-load tap changer
Figures from the Tianhua product catalogue. Lower no-load loss saves energy every hour the transformer is energised, whatever the load.
| Series | kVA range | No-load loss at 630 kVA (W) | Load loss at 630 kVA, Dyn11 (W) | No-load loss vs S11 |
|---|---|---|---|---|
| S11-M | 30–2,500 | 810 | 6,200 | — |
| S13-M | 30–3,150 | 570 | 6,200 | 30% lower |
| S13-M·RL | 30–3,150 | 570 | 6,200 | 30% lower |
| SH15-M | 30–2,500 | 320 | 6,200 | 60% lower |
| S20-M | 30–2,500 | 510 | 4,960 | 37% lower |
| S22-M | 30–2,500 | 460 | 4,460 | 43% lower |

The S11-M is the established standard series for 6–11 kV distribution networks. It uses a cold-rolled silicon steel core and a fully sealed corrugated tank, so no conservator or oil maintenance is needed.
| Rating | 30–2,500 kVA |
|---|---|
| HV / LV | 6 / 6.3 / 10 / 10.5 / 11 kV to 0.4 kV |
| Tapping | ±5% or ±2×2.5% |
| Vector group | Yyn0 or Dyn11 |
| Model | kVA | No-load loss (W) | Load loss (W) Dyn11 / Yyn0 | No-load current (%) | Impedance (%) |
|---|---|---|---|---|---|
| S11-M-100 | 100 | 200 | 1580/1500 | 1.8 | 4.0 |
| S11-M-250 | 250 | 400 | 3200/3050 | 1.4 | 4.0 |
| S11-M-400 | 400 | 570 | 4520/4300 | 1.3 | 4.0 |
| S11-M-630 | 630 | 810 | 6200 | 1.1 | 4.5 |
| S11-M-1000 | 1,000 | 1,150 | 10300 | 1.0 | 4.5 |
| S11-M-1600 | 1,600 | 1,640 | 14500 | 0.8 | 4.5 |
| S11-M-2500 | 2,500 | 2,700 | 20700 | 0.6 | 5.0 |
Load loss shown as Dyn11 / Yyn0. See the complete table →

The S13-M keeps the same sizes and connections as the S11-M but with a better core, giving 30% lower no-load loss at 630 kVA. It is the usual choice when a utility asks for a low-loss 10 kV transformer.
| Rating | 30–3,150 kVA |
|---|---|
| HV / LV | 6 / 6.3 / 10 kV to 0.4 kV |
| Tapping | ±5% or ±2×2.5% |
| Vector group | Yyn0 or Dyn11 |
| Model | kVA | No-load loss (W) | Load loss Dyn11 (W) | Load loss Yyn0 (W) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|---|---|
| S13-M-100 | 100 | 150 | 1,580 | 1,500 | 1.8 | 4.0 |
| S13-M-250 | 250 | 290 | 3,200 | 3,050 | 1.4 | 4.0 |
| S13-M-400 | 400 | 410 | 4,520 | 4,300 | 1.3 | 4.0 |
| S13-M-630 | 630 | 570 | 6,200 | 6,200 | 1.1 | 4.5 |
| S13-M-1000 | 1,000 | 830 | 10,300 | 10,300 | 1.0 | 4.5 |
| S13-M-1600 | 1,600 | 1,170 | 14,500 | 14,500 | 0.8 | 4.5 |
| S13-M-2500 | 2,500 | 1,780 | 20,700 | 20,700 | 0.7 | To order |

The S13-M·RL uses a three-dimensional wound core: three identical core frames arranged in a triangle. The magnetic path is symmetric and has no joints, which lowers no-load current and noise compared with a stacked core.
| Rating | 30–3,150 kVA |
|---|---|
| HV / LV | 6 / 6.3 / 10 kV to 0.4 kV |
| Core | 3D wound, triangle arrangement |
| Vector group | Yyn0 or Dyn11 |
| Model | kVA | No-load loss (W) | Load loss Dyn11 (W) | Load loss Yyn0 (W) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|---|---|
| S13-M·RL-100 | 100 | 150 | 1,580 | 1,500 | 1.8 | 4.0 |
| S13-M·RL-250 | 250 | 290 | 3,200 | 3,050 | 1.4 | 4.0 |
| S13-M·RL-400 | 400 | 410 | 4,520 | 4,300 | 1.3 | 4.0 |
| S13-M·RL-630 | 630 | 570 | 6,200 | 6,200 | 1.1 | 4.5 |
| S13-M·RL-1000 | 1,000 | 830 | 10,300 | 10,300 | 1.0 | 4.5 |
| S13-M·RL-1600 | 1,600 | 1,170 | 14,500 | 14,500 | 0.8 | 4.5 |
| S13-M·RL-2500 | 2,500 | 1,780 | 20,700 | 20,700 | 0.7 | To order |

The SH15-M uses an amorphous alloy core. At 630 kVA its no-load loss is 320 W, 60% lower than the S11-M. It suits networks where transformers run lightly loaded for long hours. The SBH15-M version has a foil low-voltage winding.
| Rating | 30–2,500 kVA |
|---|---|
| HV / LV | 6 / 6.3 / 10 / 10.5 / 11 kV to 0.4 kV |
| Core | Amorphous alloy |
| Vector group | Dyn11 (Yyn0 with three-limb core) |
| Model | kVA | No-load loss (W) | Load loss (W) Dyn11 / Yyn0 | No-load current (%) | Impedance (%) |
|---|---|---|---|---|---|
| SH15-M-100 | 100 | 75 | 1580/1500 | 0.90 | 4.0 |
| SH15-M-250 | 250 | 140 | 3200/3050 | 0.60 | 4.0 |
| SH15-M-400 | 400 | 200 | 4520/4300 | 0.50 | 4.0 |
| SH15-M-630 | 630 | 320 | 6200 | 0.30 | 4.5 |
| SH15-M-1000 | 1,000 | 450 | 10300 | 0.30 | 4.5 |
| SH15-M-1600 | 1,600 | 630 | 14500 | 0.20 | 4.5 |
| SH15-M-2500 | 2,500 | 900 | 21200 | 0.20 | 5.0 |
Load loss shown as Dyn11 / Yyn0. See the complete table →

The S20-M meets energy efficiency grade 2 and the S22-M meets grade 1 under GB 20052-2020. At 630 kVA, no-load loss is 510 W for the S20-M and 460 W for the S22-M. Choose them when the project specifies an efficiency grade.
| Rating | 30–2,500 kVA |
|---|---|
| HV / LV | 6 / 6.3 / 10 kV to 0.4 kV |
| Efficiency | S20-M grade 2 · S22-M grade 1 |
| Vector group | Yyn0 or Dyn11 |
S20-M (grade 2)
| Model | kVA | No-load loss (W) | Load loss Dyn11 (W) | Load loss Yyn0 (W) | Impedance (%) |
|---|---|---|---|---|---|
| S20-M-100 | 100 | 135 | 1,265 | 1,200 | 4.0 |
| S20-M-250 | 250 | 260 | 2,560 | 2,440 | 4.0 |
| S20-M-400 | 400 | 370 | 3,615 | 3,440 | 4.0 |
| S20-M-630 | 630 | 510 | 4,960 | 4,960 | 4.5 |
| S20-M-1000 | 1,000 | 745 | 8,240 | 8,240 | 4.5 |
| S20-M-1600 | 1,600 | 1,050 | 11,600 | 11,600 | 4.5 |
| S20-M-2500 | 2,500 | 1,440 | 14,840 | 14,840 | 5.0 |
S22-M (grade 1)
| Model | kVA | No-load loss (W) | Load loss Dyn11 (W) | Load loss Yyn0 (W) | Impedance (%) |
|---|---|---|---|---|---|
| S22-M-100 | 100 | 120 | 1,140 | 1,080 | 4.0 |
| S22-M-250 | 250 | 230 | 2,300 | 2,195 | 4.0 |
| S22-M-400 | 400 | 330 | 3,250 | 3,095 | 4.0 |
| S22-M-630 | 630 | 460 | 4,460 | 4,460 | 4.5 |
| S22-M-1000 | 1,000 | 665 | 7,415 | 7,415 | 4.5 |
| S22-M-1600 | 1,600 | 940 | 10,440 | 10,440 | 4.5 |
| S22-M-2500 | 2,500 | 1,280 | 13,360 | 13,360 | 5.0 |

For 35 kV substations and plant step-down, Tianhua builds the S11 series with an off-circuit tap changer and the SZ11 series with an on-load tap changer for voltage regulation under load.
| Rating | 630–31,500 kVA |
|---|---|
| HV | 35 kV (35–38.5 kV) |
| LV | 3.15 / 6.3 / 10.5 kV and others |
| Tap changer | Off-circuit (S11) or on-load ±3×2.5% (SZ11) |
| Model | kVA | Vector group | HV (kV) | LV (kV) | No-load loss (W) | Load loss (W) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|---|---|---|---|
| S11-1000 | 1,000 | Yd11 | 35 | 3.15 / 6.3 / 10.5 | 1,150 | 11,540 | 1.00 | 6.5 |
| S11-2500 | 2,500 | Yd11 | 35 | 3.15 / 6.3 / 10.5 | 2,560 | 19,670 | 0.60 | 6.5 |
| S11-5000 | 5,000 | Yd11 | 35–38.5 | 3.15 / 6.3 / 10.5 | 4,320 | 31,380 | 0.48 | 7.0 |
| S11-10000 | 10,000 | YNd11 | 35–38.5 | 3.15–11 | 8,700 | 45,300 | 0.42 | 7.5 |
| S11-20000 | 20,000 | YNd11 | 35–38.5 | 3.15–11 | 14,400 | 79,500 | 0.40 | 8.0 |
| S11-31500 | 31,500 | YNd11 | 35–38.5 | 3.15–11 | 20,220 | 112,900 | 0.32 | 8.0 |
S11 off-circuit series shown. See the complete table →
Designed and tested to GB 1094 and IEC 60076. Every unit gets routine tests before shipment, with the test report supplied. These cover ratio, vector group, winding resistance, no-load and load loss, impedance, and applied and induced voltage. Type tests and witness testing are available on request. Other voltage ratios, such as 11 kV, 13.8 kV or 33 kV, can be built to your specification.
Jiangsu Tianhua Transformer Co., Ltd. is a manufacturer, not a trading company. Every series on this page is designed, wound, assembled and tested in our plant in Xuzhou, Jiangsu, China. You talk directly to our engineers, and every unit ships with its routine test report.
They share the same kVA ratings and connections but have different loss levels. At 630 kVA, no-load loss is 810 W for S11-M, 570 W for S13-M and 460 W for S22-M. S22-M meets energy efficiency grade 1 under GB 20052-2020.
The SH15-M amorphous alloy series: 320 W at 630 kVA, 60% lower than the S11-M.
Yes. The catalogue series are 50 Hz, but we design other voltage ratios, 60 Hz versions and IEC or IEEE requirements to your specification.
Yes. The 10 kV distribution series use fully sealed corrugated tanks with no conservator, so the oil does not contact air and needs no routine maintenance.
Tell us the kVA, voltage and standard. We reply with a datasheet and price within 24 hours.