Factory-direct transformer manufacturer · Xuzhou, China

IEC 60076 · IEEE C57.12 · 50 Hz and 60 Hz designs

S11-M 10kV Oil-Immersed Distribution Transformer, 30–2,500 kVA

S11-M 10kV Oil-Immersed Distribution Transformer, 30–2,500 kVA

Specifications

Quick answer

The S11-M is a fully sealed, three-phase oil-immersed distribution transformer for 6–11 kV networks, rated 30 to 2,500 kVA with 0.4 kV output. It has no oil conservator and needs no routine oil maintenance. It is made by Jiangsu Tianhua Transformer in Xuzhou, China, to GB 1094 and IEC 60076.

SeriesS11-M, three-phase, fully sealed
Rating30–2,500 kVA
HV / LV6 / 6.3 / 10 / 10.5 / 11 kV to 0.4 kV
Vector groupDyn11 or Yyn0
Tapping±5% or ±2 × 2.5%, off-circuit
No-load loss100 W (30 kVA) to 2,700 W (2,500 kVA)
WindingsOxygen-free copper
StandardsGB 1094, IEC 60076
Lead timeTypically 4–6 weeks after drawing approval
ManufacturerJiangsu Tianhua Transformer Co., Ltd., Xuzhou, China

Get a quote in 24 hoursEmail our engineers

Rating table · Design · How to order · S11 vs S13 vs S20 · FAQ

S11-M 10 kV rating table

kVANo-load loss (W)Load loss (W) Dyn11 / Yyn0No-load current (%)Impedance (%)
30100630 / 6002.34.0
50130910 / 8702.04.0
631501,090 / 1,0401.94.0
801801,310 / 1,2501.94.0
1002001,580 / 1,5001.84.0
1252401,890 / 1,8001.74.0
1602802,310 / 2,2001.64.0
2003402,730 / 2,6001.54.0
2504003,200 / 3,0501.44.0
3154803,830 / 3,6501.44.0
4005704,520 / 4,3001.34.0
5006805,410 / 5,1001.24.0
6308106,2001.14.5
8009807,5001.04.5
1,0001,15010,3001.04.5
1,2501,36012,8000.94.5
1,6001,64014,5000.84.5
2,0002,28017,8200.65.0
2,5002,70020,7000.65.0

Load loss before the slash applies to Dyn11 or Yzn11, after the slash to Yyn0. Capacity, voltage ratio, vector group, impedance, losses and dimensions can be designed to your specification.

Design and construction

Key advantages

  • Core of stacked imported cold-rolled silicon steel, for low no-load loss and current
  • Oxygen-free copper windings: double-layer cylindrical LV up to 500 kVA, double or four-helix from 630 kVA
  • Dyn11 connection reduces harmonics on the network
  • Fully sealed corrugated tank: oil expansion is absorbed by the fins, so no conservator
  • No core lifting needed after normal transport: install, test and energise

Type designation: S11-M-□/□

  • S: three-phase
  • 11: performance level code
  • M: fully sealed
  • First □: rated capacity (kVA)
  • Second □: voltage class (kV)

Example: S11-M-630/10 is a 630 kVA, 10 kV fully sealed transformer.

Applications

  • Urban, rural and plant distribution networks
  • Residential and commercial buildings
  • Factories, mines and agricultural sites
  • Pumping stations and small industrial loads

For indoor or fire-sensitive rooms, choose a dry-type transformer. For stricter loss limits, see S13 or S20 / S22.

Standards and testing

Designed and tested to GB 1094 and IEC 60076. Every unit receives routine tests before shipment, and the test report is sent to you before the unit leaves the factory:

  • voltage ratio and vector group
  • winding resistance
  • no-load loss and current; load loss and impedance
  • applied and induced voltage tests

Type tests and third-party witness testing are available on request.

How to order

Send us

  • rated power (kVA) and quantity
  • HV and LV voltage, vector group and tapping range
  • standard (GB, IEC or your utility specification) and frequency
  • any loss limits or efficiency rule
  • site conditions: altitude, ambient temperature, coastal or industrial air
  • destination port and preferred Incoterm

What happens next

  • datasheet and price within 24 hours
  • drawings for your approval
  • production, typically 4–6 weeks after drawing approval and advance payment
  • routine tests and test report; witness test on request
  • export packing and shipping, oil-filled and ready to install

Shipping policy · Terms and conditions

S11 vs S13 vs S20 / S22 vs amorphous

SeriesCoreWhen to choose
S11-M (this page)Stacked silicon steelLowest first cost where losses are not evaluated
S13-MSilicon steel, lower-loss designLower no-load loss than S11; common choice for utility tenders
S20 / S22Low-loss silicon steelStrict efficiency rules and high energy prices
SBH15 amorphousAmorphous alloyLowest no-load loss for lightly loaded networks

Compare offers by total cost of ownership, not price alone. See how in the selection guide.

Who makes this transformer

Transformer workshop at the Tianhua factory in Xuzhou, China

Jiangsu Tianhua Transformer Co., Ltd. designs, builds and tests this transformer in its own 107,000 m² plant in Xuzhou, Jiangsu, China. Founded in 2013, Tianhua is a manufacturer, not a trading company: you deal directly with our engineers, and inspectors are welcome to witness the factory acceptance test.

  • 500+ employees, including 7 senior engineers
  • ISO 9001 quality system; IEC, IEEE / ANSI and GB designs
  • Exported to more than 30 countries and regions

About Tianhua · Factory and testing · Certificates · Projects

Frequently asked questions

What is the no-load loss of a 630 kVA S11 transformer?

810 W, with load loss of 6,200 W, no-load current of 1.1% and impedance of 4.5%.

Does the S11-M need oil maintenance?

No. The fully sealed corrugated tank keeps the oil away from air, so there is no conservator and no routine oil treatment.

S11 or S13: which should I buy?

S13 has lower no-load loss than S11. Choose S13 or S20 / S22 where losses are evaluated in the tender, and S11 where first cost matters most.

What does S11-M-630/10 mean?

S is three-phase, 11 is the performance level, M means fully sealed, 630 is the rating in kVA and 10 is the voltage class in kV.

How long does an S11-M transformer take to make?

Typically 4–6 weeks after drawing approval and advance payment. We confirm the date for your quantity in the quotation.

Can the S11-M be made for other voltages or standards?

Yes. Capacity, voltage ratio, vector group, impedance and losses can be designed to your specification and standard.

How is the S11-M shipped?

In a container or on a flat-rack, filled with oil and ready to install. Sealed units do not need core lifting after normal transport.

What warranty does Tianhua give?

The warranty is 1 to 2 years depending on the product and size, confirmed in the quotation and sales contract.

Get a quotation for the S11-M distribution transformer

Send capacity, voltage ratio, standard, quantity and destination. Our engineers reply with a datasheet and price within 24 hours.

Email sale@thatransformer.comWhatsAppCall Ivy Xiao

Data from the Tianhua product catalogue. Written by the Tianhua Transformer engineering team, Xuzhou, China. Last updated November 2026.

Routine test report

Every unit tested before shipment

Factory-direct

Built in our Xuzhou plant

Built to your spec

IEC, IEEE/ANSI or GB

Quote in 24 hours

Datasheet and price from our engineers

More from our factory

Power, distribution, dry-type and substation equipment, all designed, built and tested in our Xuzhou plant.

View all products
Need several units or a full project?

Send your single-line diagram or bill of quantities. Our engineers reply with a datasheet and price within 24 hours.