The S13-M is a fully sealed oil-immersed distribution transformer for 6–10 kV networks, rated 30–3,150 kVA with 0.4 kV output. Its no-load loss is on average 37% lower than the S11 series and its noise about 20% below JB/T 10088-2004. Made by Jiangsu Tianhua Transformer Co., Ltd. in Xuzhou, China.
Series
S13-M, three-phase, fully sealed
Rating
30–3,150 kVA
HV / LV
6 / 6.3 / 10 kV to 0.4 kV (11 kV and other ratios built to order)
Vector group
Yyn0 or Dyn11
Tapping
±5% or ±2×2.5%
No-load loss
80 W (30 kVA) to 2,100 W (3,150 kVA)
Certification
National PCCC energy-saving certified product
Manufacturer
Jiangsu Tianhua Transformer Co., Ltd., Xuzhou, China
No-load loss on average 37% lower than S11 transformers
Noise about 20% lower than JB/T 10088-2004
Optimised core and winding structure developed by Tianhua from the S11 platform
Fully sealed corrugated tank: no conservator, no oil maintenance
Ideal for urban and rural distribution network centres
Type designation: S13-M-□/□
S: three-phase
13: performance level code
M: fully sealed
□: rated capacity (kVA)
□: voltage class (kV)
S13-M 10kV rating table
Model
kVA
No-load loss (W)
Load loss Dyn11 (W)
Load loss Yyn0 (W)
No-load current (%)
Impedance (%)
S13-M-30
30
80
630
600
2.3
4.0
S13-M-50
50
100
910
870
2.0
4.0
S13-M-63
63
110
1,090
1,040
1.9
4.0
S13-M-80
80
130
1,310
1,250
1.9
4.0
S13-M-100
100
150
1,580
1,500
1.8
4.0
S13-M-125
125
170
1,890
1,800
1.7
4.0
S13-M-160
160
200
2,310
2,200
1.6
4.0
S13-M-200
200
240
2,730
2,600
1.5
4.0
S13-M-250
250
290
3,200
3,050
1.4
4.0
S13-M-315
315
340
3,830
3,650
1.4
4.0
S13-M-400
400
410
4,520
4,300
1.3
4.0
S13-M-500
500
480
5,410
5,150
1.2
4.0
S13-M-630
630
570
6,200
6,200
1.1
4.5
S13-M-800
800
700
7,500
7,500
1.0
4.5
S13-M-1000
1,000
830
10,300
10,300
1.0
4.5
S13-M-1250
1,250
970
12,000
12,000
0.9
4.5
S13-M-1600
1,600
1,170
14,500
14,500
0.8
4.5
S13-M-2000
2,000
1,510
17,800
17,800
0.8
To order
S13-M-2500
2,500
1,780
20,700
20,700
0.7
To order
S13-M-3150
3,150
2,100
24,300
24,300
0.7
To order
Impedance for 2000–3150 kVA is designed to customer requirements.
Data from the Tianhua product catalogue. Capacity, voltage ratio, vector group, impedance, losses and dimensions can be designed to your specification.
Applications
Urban and rural distribution networks
Residential and commercial buildings
Factories, workshops and industrial parks
Pole, pad and substation installations
Standards and testing
Designed and tested to GB 1094 and IEC 60076; loss levels to the series data above. Routine tests on every unit before shipment (ratio, vector group, winding resistance, no-load and load loss, impedance, applied and induced voltage) with the test report supplied. Type tests and third-party witness testing on request.
How to order
Send us
rated power and quantity
primary and secondary voltage, vector group and tapping range
standard (IEC, IEEE / ANSI, GB or your utility specification) and frequency
any loss limits or efficiency rule
site conditions: altitude, ambient temperature, indoor or outdoor, corrosion
destination port and preferred Incoterm
What happens next
datasheet and price within 24 hours
drawings for your approval
production, typically 4–6 weeks after drawing approval and advance payment
routine tests and test report; witness test on request
Jiangsu Tianhua Transformer Co., Ltd. designs, builds and tests this transformer in its own 107,000 m² plant in Xuzhou, Jiangsu, China. Founded in 2013, Tianhua is a manufacturer, not a trading company: you deal directly with our engineers, and inspectors are welcome to witness the factory acceptance test.
500+ employees, including 7 senior engineers
ISO 9001 quality system; IEC, IEEE / ANSI and GB designs
What is the no-load loss of a 1000 kVA S13 transformer?
A 1000 kVA S13-M transformer has a no-load loss of 830 W and a load loss of 10,300 W, with 1.0% no-load current and 4.5% impedance.
How does S13 compare with S11?
S13 cuts no-load loss by about 37% on average. For example, at 400 kVA the no-load loss falls from 570 W (S11) to 410 W (S13) while load loss stays at 4,520 W.
Can you build S13 transformers for 11 kV or 415 V?
Yes. The table shows the standard 10 kV series; we design S13 transformers for 11 kV, 0.415 kV and other ratios to your specification.
How long does the S13-M distribution transformer take to make?
Typically 4–6 weeks for standard units after drawing approval and advance payment. We confirm the date for your quantity in the quotation.
Can the S13-M distribution transformer be built to my specification?
Yes. Rating, voltage ratio, vector group, impedance, losses, accessories and dimensions can be designed to your specification and standard.
How is the S13-M distribution transformer shipped?
In a container or on a flat-rack, filled with oil and ready to install. Sealed units do not need core lifting after normal transport.
What warranty does Tianhua give?
The warranty is 1 to 2 years depending on the product and size, confirmed in the quotation and sales contract.