S20 and S22 are Tianhua’s energy-efficiency oil-immersed distribution transformers to GB 20052-2020: S20-M meets energy efficiency grade 2 and S22-M grade 1, the lowest-loss level. Both cover 30–2,500 kVA at 6–10 kV / 0.4 kV.
Lowest-loss oil distribution transformers in our range
S22 grade 1 losses are lower again than S20 grade 2
Noise about 20% lower than JB/T 10088-2016
New core and coil structure designed in-house
Fully sealed tank, maintenance-free
Type designation: S20-M-□/□-NX2 and S22-M-□/□-NX1
S: three-phase
20 / 22: performance level code
M: fully sealed
□: rated capacity (kVA) / voltage class (kV)
NX2 / NX1: energy efficiency grade 2 / grade 1
S20-M rating table (energy efficiency grade 2)
Model
kVA
No-load loss (W)
Load loss Dyn11 (W)
Load loss Yyn0 (W)
Impedance (%)
S20-M-30
30
70
505
480
4.0
S20-M-50
50
90
730
695
4.0
S20-M-63
63
100
870
830
4.0
S20-M-80
80
115
1,050
1,000
4.0
S20-M-100
100
135
1,265
1,200
4.0
S20-M-125
125
150
1,510
1,440
4.0
S20-M-160
160
180
1,850
1,760
4.0
S20-M-200
200
215
2,185
2,080
4.0
S20-M-250
250
260
2,560
2,440
4.0
S20-M-315
315
305
3,065
2,920
4.0
S20-M-400
400
370
3,615
3,440
4.0
S20-M-500
500
430
4,330
4,120
4.0
S20-M-630
630
510
4,960
4,960
4.5
S20-M-800
800
630
6,000
6,000
4.5
S20-M-1000
1,000
745
8,240
8,240
4.5
S20-M-1250
1,250
870
9,600
9,600
4.5
S20-M-1600
1,600
1,050
11,600
11,600
4.5
S20-M-2000
2,000
1,225
14,640
14,640
5.0
S20-M-2500
2,500
1,440
14,840
14,840
5.0
S22-M rating table (energy efficiency grade 1)
Model
kVA
No-load loss (W)
Load loss Dyn11 (W)
Load loss Yyn0 (W)
Impedance (%)
S22-M-30
30
65
455
430
4.0
S22-M-50
50
80
655
625
4.0
S22-M-63
63
90
785
745
4.0
S22-M-80
80
105
945
900
4.0
S22-M-100
100
120
1,140
1,080
4.0
S22-M-125
125
135
1,360
1,295
4.0
S22-M-160
160
160
1,665
1,585
4.0
S22-M-200
200
190
1,970
1,870
4.0
S22-M-250
250
230
2,300
2,195
4.0
S22-M-315
315
270
2,760
2,630
4.0
S22-M-400
400
330
3,250
3,095
4.0
S22-M-500
500
385
3,900
3,710
4.0
S22-M-630
630
460
4,460
4,460
4.5
S22-M-800
800
560
5,400
5,400
4.5
S22-M-1000
1,000
665
7,415
7,415
4.5
S22-M-1250
1,250
780
8,640
8,640
4.5
S22-M-1600
1,600
940
10,440
10,440
4.5
S22-M-2000
2,000
1,085
13,180
13,180
5.0
S22-M-2500
2,500
1,280
13,360
13,360
5.0
Data from the Tianhua product catalogue. Capacity, voltage ratio, vector group, impedance, losses and dimensions can be designed to your specification.
Applications
Utility network upgrades with loss-evaluation tenders
Commercial buildings and data rooms
Renewable and industrial projects with low-loss requirements
Standards and testing
Designed and tested to GB 1094 and IEC 60076; loss levels to the series data above. Routine tests on every unit before shipment (ratio, vector group, winding resistance, no-load and load loss, impedance, applied and induced voltage) with the test report supplied. Type tests and third-party witness testing on request. Energy efficiency grades to GB 20052-2020.
How to order
Send us
rated power and quantity
primary and secondary voltage, vector group and tapping range
standard (IEC, IEEE / ANSI, GB or your utility specification) and frequency
any loss limits or efficiency rule
site conditions: altitude, ambient temperature, indoor or outdoor, corrosion
destination port and preferred Incoterm
What happens next
datasheet and price within 24 hours
drawings for your approval
production, typically 4–6 weeks after drawing approval and advance payment
routine tests and test report; witness test on request
Jiangsu Tianhua Transformer Co., Ltd. designs, builds and tests this transformer in its own 107,000 m² plant in Xuzhou, Jiangsu, China. Founded in 2013, Tianhua is a manufacturer, not a trading company: you deal directly with our engineers, and inspectors are welcome to witness the factory acceptance test.
500+ employees, including 7 senior engineers
ISO 9001 quality system; IEC, IEEE / ANSI and GB designs
What is the difference between S20 and S22 transformers?
Both follow GB 20052-2020. S20 is energy efficiency grade 2 and S22 is grade 1. At 1000 kVA, no-load loss is 745 W for S20 and 665 W for S22, and load loss is 8,240 W versus 7,415 W.
What is the no-load loss of a 630 kVA S22 transformer?
510 W for S20-M-630 and 460 W for S22-M-630, both with 4.5% impedance.
Are S20 and S22 suitable for export tenders?
Yes. We quote them against IEC 60076 and your loss-capitalisation formula, and supply routine test reports with every unit.
How long does the S20 / S22 distribution transformer take to make?
Typically 4–6 weeks for standard units after drawing approval and advance payment. We confirm the date for your quantity in the quotation.
Can the S20 / S22 distribution transformer be built to my specification?
Yes. Rating, voltage ratio, vector group, impedance, losses, accessories and dimensions can be designed to your specification and standard.
How is the S20 / S22 distribution transformer shipped?
In a container or on a flat-rack, filled with oil and ready to install. Sealed units do not need core lifting after normal transport.
What warranty does Tianhua give?
The warranty is 1 to 2 years depending on the product and size, confirmed in the quotation and sales contract.