Factory-direct transformer manufacturer · Xuzhou, China

IEC 60076 · IEEE C57.12 · 50 Hz and 60 Hz designs

Data Center Solutions

Transformers for AI Data Centers

Data centers · hyperscale · colocation · edge

From utility interconnection to indoor power distribution, Tianhua supplies 220 kV oil-immersed power transformers for campus substations and cast-resin dry-type transformers for building-level MV/LV distribution.

220 kV transformer in a data center campus substation illustration
31.5–360 MVA220 kV oil-immersed main transformer
30–2,500 kVASC(B)13 cast-resin range
K4 · K13 · K20options for harmonic loads
24 hquotation reply

Transformer options for grid connection and indoor distribution

Select the transformer for your part of the project. Utility interconnection requirements and the project single-line diagram determine the incoming voltage and equipment ratings.

Data center challenges we solve

Transformers run 24/7, so no-load loss is paid every hour.

Our answer: At 1,600 kVA the catalogue no-load loss falls from 2,450 W (SC(B)10) to 760 W (SC(B)H15). The saving is shown in kWh below.

UPS and server power supplies create harmonics.

Our answer: K-factor dry-type transformers (K4, K13, K20) have harmonic-rated windings, 115/150°C rise options and 220°C insulation.

Fire safety indoors.

Our answer: Cast resin and VPI dry-type transformers contain no oil. SG(B)13 has class H (180°C) insulation and 120% continuous overload.

2N and N+1 redundancy needs matched units.

Our answer: Units built to the same design and tested before shipment, with matched impedance on request.

Power path: utility to rack

Example power path for a campus with a high-voltage utility connection. The site can connect at medium voltage where the utility and project design allow it.

  1. Utility gridProject-specific

    The utility confirms the incoming voltage and point of connection.

  2. Tianhua oil-immersed power transformer

    Campus substationHV to MV

    Where the site connects at 220 kV, the main transformer feeds the campus medium-voltage network.

  3. Tianhua KYN28A-12 medium-voltage switchgear

    Campus MV distributionProject-specific

    Medium-voltage feeders distribute power to the buildings. KYN28A-12 is an option for the 12 kV equipment class.

  4. Tianhua SC(B)13 cast-resin dry-type transformer

    Indoor MV/LV transformerMV to LV

    Cast-resin dry-type units step down the building feeder voltage for indoor low-voltage distribution.

  5. LV switchgear and UPSBuilding LV

    Low-voltage switchgear feeds UPS and other building loads as specified. Review harmonic requirements for transformer circuits serving nonlinear loads.

Building or expanding a data center?

Send your single-line diagram, incoming voltage, capacity per transformer and delivery location. We reply with a proposal and price within 24 hours.

Problems each product solves, from our catalogue

These points come straight from the Tianhua product catalogue for our dry-type transformers. The catalogue names power stations, factories, hospitals, airports, tunnels, chemical plants and nuclear power plants as their ideal applications.

SC(B)13 cast resin transformer by Tianhua
SC(B)13 cast resin transformer

Solves: Fire, smoke and partial discharge risk indoors

  • No-load loss 30% lower than SC(B)10; load loss over 10% lower than SC(B)11
  • Vacuum-cast resin keeps partial discharge to 5 pC or less
  • Glass-fibre materials are self-extinguishing, do not arc in a short circuit and give off no harmful gas
  • Noise 10–15 dB below JB/T 10088-2016; maintenance-free
SCB18 grade 1 dry-type transformer by Tianhua
SCB18 grade 1 dry-type transformer

Solves: Loss limits and high-load, fire-sensitive sites

  • Energy efficiency grade 1 to GB 20052-2020
  • Strong short-circuit resistance, low maintenance and high efficiency; safe, fireproof and pollution-free
  • Short-time overload under forced-air cooling; moisture-proof for humid environments
  • Smart temperature control starts and stops the fans automatically, with alarm and trip
SCB14 grade 2 dry-type transformer by Tianhua
SCB14 grade 2 dry-type transformer

Solves: Efficiency-grade tenders with a smaller footprint

  • Energy efficiency grade 2 to GB 20052-2020
  • Used where fire and explosion protection requirements are high
  • Small size, light weight, small floor area and low installation cost
SC(B)H15 amorphous dry-type transformer by Tianhua
SC(B)H15 amorphous dry-type transformer

Solves: Paying for no-load loss every hour of the year

  • No-load loss about 75% below the GB/T 10228 value
  • Amorphous core sealed in resin and solvent-free paint, protected against corrosion
  • Noise 5–15 dB below GB/T 10088; passed a sudden short-circuit test
  • Up to 150% rated load with forced-air cooling
SG(B)13 VPI dry-type transformer by Tianhua
SG(B)13 VPI dry-type transformer

Solves: Heat shock, overloads and smoke in a fire

  • Class H (180°C) insulation; strong against heat shock and overload
  • 120% continuous overload and 140% for 3 hours without forced cooling
  • Produces almost no smoke at high temperature or in flame
  • Can take full load immediately at ±50°C

Running-cost comparison: 1,600 kVA dry-type transformer

Catalogue no-load loss × 8,760 hours per year. In a data centre the transformer is energised all year, so this is the minimum energy it consumes.

SeriesNo-load loss (W)No-load energy per year (kWh)Saving vs SC(B)10 per year (kWh)
SC(B)102,45021,462—
SC(B)131,76515,4616,001
SCB14 (grade 2)1,76515,4616,001
SCB18 (grade 1)1,41512,3959,067
SC(B)H15 amorphous7606,65814,804

Calculated from the Tianhua catalogue. Multiply by your tariff and the number of transformers.

Recommended equipment

Additional transformer and switchgear options

Selection guide

NeedRecommendedKey data
220 kV utility interconnection220 kV oil-immersed power transformer31.5–360 MVA · OLTC
Indoor MV/LV distributionSC(B)13 cast-resin dry-type transformer30–2,500 kVA · Cast-resin insulation
UPS input / output, IT loadsK-factor dry-type transformerK4, K13, K20; 115/150°C rise; 220°C insulation
Lowest energy lossSC(B)H15 amorphous dry-type transformer760 W no-load at 1,600 kVA
Efficiency-grade specificationSCB18 grade 1 dry-type transformerGrade 1; 1,415 W no-load at 1,600 kVA
High temperature, overloadsSG(B)13 VPI dry-type transformerClass H 180°C; 120% continuous overload
20–24 kV utility supply20kV / 24kV cast resin transformer50–2,500 kVA, Dyn11, 6% impedance
MV switchingKYN28A-12 metal-clad switchgear12 kV, 42/75 kV insulation, IP4X

From our factory to your site

Real photos from our plant in Xuzhou. Every unit is built, tested, packed and shipped by our own team.

Tianhua transformer factory in Xuzhou, Jiangsu, China
Tianhua transformer factory in Xuzhou, Jiangsu, China
Vacuum drying ovens for transformer active parts
Vacuum drying ovens for transformer active parts
Distribution transformers on the Tianhua production floor
Distribution transformers on the Tianhua production floor

What to send for a data center quotation

  • Single-line diagram and redundancy design (N+1, 2N)
  • Utility incoming voltage, primary and secondary voltages, and capacity per transformer
  • Vector group and impedance where specified
  • Load type: UPS, IT, mechanical; required K-factor
  • Efficiency target or loss limits
  • Enclosure IP rating, fans and temperature controller
  • Standard (IEC 60076-11, GB, IEEE) and noise limits
  • Quantity, site and required delivery date

Manufacturer facts

ManufacturerJiangsu Tianhua Transformer Co., Ltd. (brand THA 天华)
Business typeFactory and manufacturer, not a trading company
LocationNo. 105 Xuhai Road, Economic and Technological Development Zone, Xuzhou, Jiangsu, China
Products for this application220 kV oil-immersed power transformers, SCB13, SCB14 (grade 2), SCB18 (grade 1), SC(B)H15 amorphous, SG(B)13 VPI and 20 kV cast resin dry-type transformers, K-factor transformers, KYN28A-12 switchgear, YB prefabricated substations
StandardsGB 1094 / IEC 60076; dry-type to GB 1094.11 / IEC 60076-11; energy efficiency to GB 20052-2020
Export marketsIndonesia, Kazakhstan, Vietnam, Russia, the Philippines and others
Sales contactIvy Xiao · +86 136 8498 9973 · sale@thatransformer.com

Why buyers work with Tianhua

Factory, not traderDesigned, built and tested in our own plant in Xuzhou, Jiangsu, China.
Test report with every unitRoutine tests before shipment; type and witness tests on request.
Built to your specificationVoltage, vector group, impedance, losses, enclosure and accessories to order.
Quote in 24 hoursTalk directly to our engineers and sales contact Ivy Xiao.

Related article: Data Center Transformers: Dry-Type or Oil, Sizing and Redundancy · All articles

Frequently asked questions

Who supplies dry-type transformers for data centers from China?

Jiangsu Tianhua Transformer Co., Ltd. in Xuzhou, Jiangsu, manufactures cast resin, amorphous alloy, VPI and K-factor dry-type transformers, including energy efficiency grade 1 (SCB18) units, plus 12 kV switchgear for data centre power.

Why do data centers use dry-type transformers?

They contain no oil, so they are safer indoors and need no oil containment. Cast resin windings also resist humidity and dust.

What K-factor do I need for UPS loads?

K4 suits moderate non-linear loads, K13 suits typical IT and UPS loads, and K20 suits heavy harmonic loads. Send your load profile and our engineers will confirm the rating.

Which dry-type transformer has the lowest running loss?

The SC(B)H15 amorphous alloy series: 760 W no-load loss at 1,600 kVA, compared with 2,450 W for SC(B)10 (catalogue figures).

Do you supply matching switchgear?

Yes. We supply KYN28A-12 metal-clad withdrawable switchgear for the 12 kV side, and YB prefabricated substations for outdoor installations.

Send your single-line diagram or equipment list. Our engineers reply with a proposal and price within 24 hours.