Data centers · hyperscale · colocation · edge
From utility interconnection to indoor power distribution, Tianhua supplies 220 kV oil-immersed power transformers for campus substations and cast-resin dry-type transformers for building-level MV/LV distribution.

Select the transformer for your part of the project. Utility interconnection requirements and the project single-line diagram determine the incoming voltage and equipment ratings.
UTILITY GRID CONNECTION220 kV Oil-Immersed Power TransformerFor data center campuses with a 220 kV utility connection. Steps grid voltage down to the campus medium-voltage network.31.5–360 MVA · OLTCView 220 kV Transformer →
INDOOR MV/LV DISTRIBUTIONSC(B)13 Cast-Resin Dry-Type TransformerFor indoor electrical rooms. Steps medium voltage down to supply building-level low-voltage switchgear.30–2,500 kVA · Cast-resin insulationView SC(B)13 Transformer →Transformers run 24/7, so no-load loss is paid every hour.
Our answer: At 1,600 kVA the catalogue no-load loss falls from 2,450 W (SC(B)10) to 760 W (SC(B)H15). The saving is shown in kWh below.
UPS and server power supplies create harmonics.
Our answer: K-factor dry-type transformers (K4, K13, K20) have harmonic-rated windings, 115/150°C rise options and 220°C insulation.
Fire safety indoors.
Our answer: Cast resin and VPI dry-type transformers contain no oil. SG(B)13 has class H (180°C) insulation and 120% continuous overload.
2N and N+1 redundancy needs matched units.
Our answer: Units built to the same design and tested before shipment, with matched impedance on request.
Example power path for a campus with a high-voltage utility connection. The site can connect at medium voltage where the utility and project design allow it.
Utility gridProject-specific
The utility confirms the incoming voltage and point of connection.

Campus substationHV to MV
Where the site connects at 220 kV, the main transformer feeds the campus medium-voltage network.

Campus MV distributionProject-specific
Medium-voltage feeders distribute power to the buildings. KYN28A-12 is an option for the 12 kV equipment class.

Indoor MV/LV transformerMV to LV
Cast-resin dry-type units step down the building feeder voltage for indoor low-voltage distribution.
LV switchgear and UPSBuilding LV
Low-voltage switchgear feeds UPS and other building loads as specified. Review harmonic requirements for transformer circuits serving nonlinear loads.
Building or expanding a data center?
Send your single-line diagram, incoming voltage, capacity per transformer and delivery location. We reply with a proposal and price within 24 hours.
These points come straight from the Tianhua product catalogue for our dry-type transformers. The catalogue names power stations, factories, hospitals, airports, tunnels, chemical plants and nuclear power plants as their ideal applications.

Solves: Fire, smoke and partial discharge risk indoors

Solves: Loss limits and high-load, fire-sensitive sites

Solves: Efficiency-grade tenders with a smaller footprint

Solves: Paying for no-load loss every hour of the year

Solves: Heat shock, overloads and smoke in a fire
Catalogue no-load loss × 8,760 hours per year. In a data centre the transformer is energised all year, so this is the minimum energy it consumes.
| Series | No-load loss (W) | No-load energy per year (kWh) | Saving vs SC(B)10 per year (kWh) |
|---|---|---|---|
| SC(B)10 | 2,450 | 21,462 | — |
| SC(B)13 | 1,765 | 15,461 | 6,001 |
| SCB14 (grade 2) | 1,765 | 15,461 | 6,001 |
| SCB18 (grade 1) | 1,415 | 12,395 | 9,067 |
| SC(B)H15 amorphous | 760 | 6,658 | 14,804 |
Calculated from the Tianhua catalogue. Multiply by your tariff and the number of transformers.
CAMPUS SUBSTATION220 kV Oil-Immersed Power Transformer31.5–360 MVA · OLTCView 220 kV Transformer →
INDOOR MV/LV DISTRIBUTIONSC(B)13 Cast-Resin Dry-Type Transformer30–2,500 kVA · Cast-resin insulationView SC(B)13 Transformer →
K-factor dry-type transformerK4 / K13 / K20, custom to 5,000 kVAView specifications →
SCB18 grade 1 dry-type transformerEnergy efficiency grade 1View specifications →
SC(B)H15 amorphous dry-type transformerLowest no-load loss of our dry-type rangeView specifications →
SCB14 grade 2 dry-type transformerGrade 2, smart temperature controlView specifications →
SG(B)13 VPI dry-type transformerClass H, 120% continuous overloadView specifications →
20kV / 24kV cast resin transformer20 / 22 / 24 kV, 50–2,500 kVAView specifications →
KYN28A-12 metal-clad switchgear12 kV withdrawable vacuum breakerView specifications →
YB prefabricated substationOutdoor 10 kV substationView specifications →
Three-phase pad-mounted transformer45–5,000 kVA campus distributionView specifications →| Need | Recommended | Key data |
|---|---|---|
| 220 kV utility interconnection | 220 kV oil-immersed power transformer | 31.5–360 MVA · OLTC |
| Indoor MV/LV distribution | SC(B)13 cast-resin dry-type transformer | 30–2,500 kVA · Cast-resin insulation |
| UPS input / output, IT loads | K-factor dry-type transformer | K4, K13, K20; 115/150°C rise; 220°C insulation |
| Lowest energy loss | SC(B)H15 amorphous dry-type transformer | 760 W no-load at 1,600 kVA |
| Efficiency-grade specification | SCB18 grade 1 dry-type transformer | Grade 1; 1,415 W no-load at 1,600 kVA |
| High temperature, overloads | SG(B)13 VPI dry-type transformer | Class H 180°C; 120% continuous overload |
| 20–24 kV utility supply | 20kV / 24kV cast resin transformer | 50–2,500 kVA, Dyn11, 6% impedance |
| MV switching | KYN28A-12 metal-clad switchgear | 12 kV, 42/75 kV insulation, IP4X |
Real photos from our plant in Xuzhou. Every unit is built, tested, packed and shipped by our own team.



| Manufacturer | Jiangsu Tianhua Transformer Co., Ltd. (brand THA 天华) |
|---|---|
| Business type | Factory and manufacturer, not a trading company |
| Location | No. 105 Xuhai Road, Economic and Technological Development Zone, Xuzhou, Jiangsu, China |
| Products for this application | 220 kV oil-immersed power transformers, SCB13, SCB14 (grade 2), SCB18 (grade 1), SC(B)H15 amorphous, SG(B)13 VPI and 20 kV cast resin dry-type transformers, K-factor transformers, KYN28A-12 switchgear, YB prefabricated substations |
| Standards | GB 1094 / IEC 60076; dry-type to GB 1094.11 / IEC 60076-11; energy efficiency to GB 20052-2020 |
| Export markets | Indonesia, Kazakhstan, Vietnam, Russia, the Philippines and others |
| Sales contact | Ivy Xiao · +86 136 8498 9973 · sale@thatransformer.com |
Related article: Data Center Transformers: Dry-Type or Oil, Sizing and Redundancy · All articles
Jiangsu Tianhua Transformer Co., Ltd. in Xuzhou, Jiangsu, manufactures cast resin, amorphous alloy, VPI and K-factor dry-type transformers, including energy efficiency grade 1 (SCB18) units, plus 12 kV switchgear for data centre power.
They contain no oil, so they are safer indoors and need no oil containment. Cast resin windings also resist humidity and dust.
K4 suits moderate non-linear loads, K13 suits typical IT and UPS loads, and K20 suits heavy harmonic loads. Send your load profile and our engineers will confirm the rating.
The SC(B)H15 amorphous alloy series: 760 W no-load loss at 1,600 kVA, compared with 2,450 W for SC(B)10 (catalogue figures).
Yes. We supply KYN28A-12 metal-clad withdrawable switchgear for the 12 kV side, and YB prefabricated substations for outdoor installations.
Send your single-line diagram or equipment list. Our engineers reply with a proposal and price within 24 hours.