The SCB18 is Tianhua’s grade 1 energy-efficiency cast resin dry-type transformer to GB 20052-2020, the lowest-loss level in our dry-type range. Ratings 30–2,500 kVA at 6–10 kV / 0.4 kV, no-load loss from 105 W to 2,080 W.
Series
SCB18-□/□-NX1, energy efficiency grade 1
Standard
GB 20052-2020
Rating
30–2,500 kVA
HV / LV
6 / 6.3 / 10 kV to 0.4 kV
Vector group
Yyn0 or Dyn11
Certification
National PCCC energy-saving certified product
Manufacturer
Jiangsu Tianhua Transformer Co., Ltd., Xuzhou, China
Grade 1 energy efficiency: lowest no-load loss in our dry-type range
Strong short-circuit withstand and high operating efficiency
Fire-proof and pollution-free for installation at the load centre
Short-time overload with forced-air cooling
Moisture-proof design for humid environments
Intelligent temperature control with alarm, trip and automatic fan control
Type designation: SCB18-□/□-NX1
S: three-phase
C: epoxy resin cast
B: low-voltage foil winding
18: performance level code
□: rated capacity (kVA) / voltage class (kV)
NX1: energy efficiency grade 1
SCB18 rating table (energy efficiency grade 1)
Model
kVA
No-load loss (W)
Load loss 120°C (W)
Load loss 145°C (W)
No-load current (%)
Impedance (%)
SC18-30
30
105
640
685
1.7
4.0
SC18-50
50
155
900
965
1.7
4.0
SC18-80
80
210
1,240
1,330
1.28
4.0
SC18-100
100
230
1,415
1,520
1.28
4.0
SC18-125
125
2,740
1,665
1,780
1.11
4.0
SC(B)18-160
160
310
1,915
2,050
1.11
4.0
SC(B)18-200
200
360
2,275
2,440
0.94
4.0
SC(B)18-250
250
415
2,485
2,665
0.94
4.0
SC(B)18-315
315
510
3,125
3,355
0.85
4.0
SC(B)18-400
400
570
3,590
3,850
0.85
4.0
SC(B)18-500
500
670
4,390
4,705
0.85
4.0
SC(B)18-630
630
775
5,290
5,660
0.72
4.0
SC(B)18-630
630
720
5,365
5,760
0.72
6.0
SC(B)18-800
800
875
6,265
6,715
0.72
6.0
SC(B)18-1000
1,000
1,020
7,315
7,885
0.72
6.0
SC(B)18-1250
1,250
1,205
8,720
9,335
0.72
6.0
SC(B)18-1600
1,600
1,415
10,555
11,320
0.72
6.0
SC(B)18-2000
2,000
1,760
13,005
14,005
0.6
6.0
SC(B)18-2500
2,500
2,080
15,455
16,605
0.6
6.0
Data from the Tianhua product catalogue. Capacity, voltage ratio, vector group, impedance, losses and dimensions can be designed to your specification.
Applications
Green buildings and data centres
Projects with loss-capitalised tenders
Hospitals, airports and metro
Standards and testing
Designed and tested to GB 1094.11 and IEC 60076-11. Routine tests on every unit before shipment, including partial discharge measurement, with the test report supplied. Type tests and witness testing on request. Energy efficiency grade to GB 20052-2020.
How to order
Send us
rated power and quantity
primary and secondary voltage, vector group and tapping range
standard (IEC, IEEE / ANSI, GB or your utility specification) and frequency
any loss limits or efficiency rule
site conditions: altitude, ambient temperature, indoor or outdoor, corrosion
destination port and preferred Incoterm
What happens next
datasheet and price within 24 hours
drawings for your approval
production after drawing approval and advance payment, on the date confirmed in the quotation
routine tests and test report; witness test on request
Jiangsu Tianhua Transformer Co., Ltd. designs, builds and tests this transformer in its own 107,000 m² plant in Xuzhou, Jiangsu, China. Founded in 2013, Tianhua is a manufacturer, not a trading company: you deal directly with our engineers, and inspectors are welcome to witness the factory acceptance test.
500+ employees, including 7 senior engineers
ISO 9001 quality system; IEC, IEEE / ANSI and GB designs