The SCB14 is a cast resin dry-type transformer that meets energy efficiency grade 2 of GB 20052-2020. It combines strong short-circuit withstand with low loss and low noise, rated 30–2,500 kVA at 6–10 kV / 0.4 kV. Made by Jiangsu Tianhua Transformer Co., Ltd. in Xuzhou, China.
Series
SCB14-□/□-NX2, energy efficiency grade 2
Standard
GB 20052-2020
Rating
30–2,500 kVA
HV / LV
6 / 6.3 / 10 kV to 0.4 kV
Vector group
Yyn0 or Dyn11
Certification
National PCCC energy-saving certified product
Manufacturer
Jiangsu Tianhua Transformer Co., Ltd., Xuzhou, China
Strong short-circuit withstand, low maintenance, high efficiency
Safe, fire-proof, pollution-free: can run directly at the load centre
Low partial discharge, good thermal stability, long service life
Short-time overload under forced-air cooling
Moisture-proof for humid, harsh environments
Intelligent temperature controller with auto fan start/stop, alarm and trip; small and light
Type designation: SCB14-□/□-NX2
S: three-phase
C: epoxy resin cast
B: low-voltage foil winding
14: performance level code
□: rated capacity (kVA) / voltage class (kV)
NX2: energy efficiency grade 2
SCB14 rating table (energy efficiency grade 2)
Model
kVA
No-load loss (W)
Load loss 120°C (W)
Load loss 145°C (W)
No-load current (%)
Impedance (%)
SC14-30
30
135
640
685
1.7
4.0
SC14-50
50
195
900
965
1.7
4.0
SC14-80
80
265
1,240
1,330
1.28
4.0
SC14-100
100
290
1,415
1,520
1.28
4.0
SC14-125
125
340
1,665
1,780
1.11
4.0
SC(B)14-160
160
385
1,915
2,050
1.11
4.0
SC(B)14-200
200
445
2,275
2,440
0.94
4.0
SC(B)14-250
250
515
2,485
2,665
0.94
4.0
SC(B)14-315
315
635
3,125
3,355
0.85
4.0
SC(B)14-400
400
705
3,590
3,850
0.85
4.0
SC(B)14-500
500
835
4,390
4,705
0.85
4.0
SC(B)14-630
630
965
5,290
5,660
0.72
4.0
SC(B)14-630
630
935
5,365
5,760
0.72
6.0
SC(B)14-800
800
1,095
6,265
6,715
0.72
6.0
SC(B)14-1000
1,000
1,275
7,315
7,885
0.72
6.0
SC(B)14-1250
1,250
1,505
8,720
9,335
0.72
6.0
SC(B)14-1600
1,600
1,765
10,555
11,320
0.72
6.0
SC(B)14-2000
2,000
2,195
13,005
14,005
0.6
6.0
SC(B)14-2500
2,500
2,590
15,455
16,605
0.6
6.0
630 kVA is listed with 4% and 6% impedance.
Data from the Tianhua product catalogue. Capacity, voltage ratio, vector group, impedance, losses and dimensions can be designed to your specification.
Applications
Commercial and public buildings
Data centres and hospitals
Fire-sensitive and explosion-risk sites
Standards and testing
Designed and tested to GB 1094.11 and IEC 60076-11. Routine tests on every unit before shipment, including partial discharge measurement, with the test report supplied. Type tests and witness testing on request. Energy efficiency grade to GB 20052-2020.
How to order
Send us
rated power and quantity
primary and secondary voltage, vector group and tapping range
standard (IEC, IEEE / ANSI, GB or your utility specification) and frequency
any loss limits or efficiency rule
site conditions: altitude, ambient temperature, indoor or outdoor, corrosion
destination port and preferred Incoterm
What happens next
datasheet and price within 24 hours
drawings for your approval
production after drawing approval and advance payment, on the date confirmed in the quotation
routine tests and test report; witness test on request
Jiangsu Tianhua Transformer Co., Ltd. designs, builds and tests this transformer in its own 107,000 m² plant in Xuzhou, Jiangsu, China. Founded in 2013, Tianhua is a manufacturer, not a trading company: you deal directly with our engineers, and inspectors are welcome to witness the factory acceptance test.
500+ employees, including 7 senior engineers
ISO 9001 quality system; IEC, IEEE / ANSI and GB designs