Factory-direct · SCB10 to SCB18 · 30 kVA to 2,500 kVA
Tianhua builds cast resin dry-type transformers from the SC(B)10 to the grade 1 SC(B)18, plus amorphous alloy and VPI open-wound designs. Compare the series below, then open any series for its full rating table.
Quick answer: dry-type transformers use no oil, so they are chosen for buildings, data centres, hospitals and other indoor or fire-sensitive sites. All series below cover 30–2,500 kVA at 6–10 kV to 0.4 kV. They differ mainly in loss level. At 630 kVA, no-load loss falls from 1,350 W (SC(B)10) to 775 W (SC(B)18) and 420 W (SC(B)H15 amorphous).

Standard cast resin, 10 kV and 35 kV

21% lower no-load loss than SC(B)10

29% lower no-load loss than SC(B)10

Energy efficiency grade 2 (GB 20052-2020)

Energy efficiency grade 1 (GB 20052-2020)

Amorphous alloy core, cast resin

Non-encapsulated (open-wound) VPI
Figures from the Tianhua product catalogue, at 4% impedance. Load loss is given at the 120°C reference temperature.
| Series | kVA range | No-load loss at 630 kVA (W) | Load loss at 630 kVA, 120°C (W) | No-load loss vs SC(B)10 |
|---|---|---|---|---|
| SC(B)10 | 30–2,500 | 1,350 | 5,880 | — |
| SC(B)12 | 30–2,500 | 1,070 | 5,880 | 21% lower |
| SC(B)13 | 30–2,500 | 965 | 5,290 | 29% lower |
| SC(B)14 grade 2 | 30–2,500 | 965 | 5,290 | 29% lower |
| SC(B)18 grade 1 | 30–2,500 | 775 | 5,290 | 43% lower |
| SC(B)H15 amorphous | 30–2,500 | 420 | 5,880 | 69% lower |

The SC(B)10 is the standard epoxy cast resin series. It is available for 10 kV and 35 kV systems, which makes it the usual choice when a project needs a 35 kV dry-type unit.
| Rating | 30–2,500 kVA (10 kV) |
|---|---|
| HV / LV | 6 / 6.3 / 10 kV to 0.4 kV; 35 kV series available |
| Tapping | ±5%, ±2×2.5% or +3/−1×2.5% |
| Vector group | Yyn0 or Dyn11 |
| Model | kVA | No-load loss (W) | Load loss 120°C (W) | Load loss 145°C (W) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|---|---|
| SC10-100 | 100 | 400 | 1,570 | 1,690 | 1.5 | 4.0 |
| SCB10-250 | 250 | 720 | 2,760 | 2,960 | 1.1 | 4.0 |
| SCB10-400 | 400 | 980 | 3,990 | 4,280 | 1.0 | 4.0 |
| SCB10-630 | 630 | 1,350 | 5,880 | 6,290 | 0.85 | 4.0 |
| SCB10-630 | 630 | 1,300 | 5,960 | 6,400 | 0.85 | 6.0 |
| SCB10-1000 | 1,000 | 1,770 | 8,130 | 8,760 | 0.85 | 6.0 |
| SCB10-1600 | 1,600 | 2,450 | 11,700 | 12,500 | 0.85 | 6.0 |
| SCB10-2500 | 2,500 | 3,600 | 17,100 | 18,400 | 0.7 | 6.0 |

The SC(B)12 has the same construction as the SC(B)10, with a better core and 21% lower no-load loss at 630 kVA.
| Rating | 30–2,500 kVA |
|---|---|
| HV / LV | 6 / 6.3 / 10 kV to 0.4 kV |
| Tapping | ±5%, ±2×2.5% or +3/−1×2.5% |
| Vector group | Yyn0 or Dyn11 |
| Model | kVA | No-load loss (W) | Load loss 120°C (W) | Load loss 145°C (W) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|---|---|
| SC12-100 | 100 | 320 | 1,570 | 1,690 | 1.28 | 4.0 |
| SC(B)12-250 | 250 | 575 | 2,760 | 2,960 | 0.94 | 4.0 |
| SC(B)12-400 | 400 | 785 | 3,990 | 4,280 | 0.85 | 4.0 |
| SC(B)12-630 | 630 | 1,070 | 5,880 | 6,290 | 0.72 | 4.0 |
| SC(B)12-630 | 630 | 1,040 | 5,960 | 6,400 | 0.72 | 6.0 |
| SC(B)12-1000 | 1,000 | 1,410 | 8,130 | 8,760 | 0.72 | 6.0 |
| SC(B)12-1600 | 1,600 | 1,960 | 11,730 | 12,580 | 0.72 | 6.0 |
| SC(B)12-2500 | 2,500 | 2,880 | 17,170 | 18,450 | 0.6 | 6.0 |

The SC(B)13 is the most requested low-loss cast resin series: 29% lower no-load loss than the SC(B)10 at 630 kVA, with a foil low-voltage winding in the B version.
| Rating | 30–2,500 kVA |
|---|---|
| HV / LV | 6 / 6.3 / 10 kV to 0.4 kV |
| Tapping | ±5%, ±2×2.5% or +3/−1×2.5% |
| Vector group | Yyn0 or Dyn11 |
| Model | kVA | No-load loss (W) | Load loss 120°C (W) | Load loss 145°C (W) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|---|---|
| SC13-100 | 100 | 290 | 1,415 | 1,520 | 1.28 | 4.0 |
| SC(B)13-250 | 250 | 515 | 2,485 | 2,665 | 0.94 | 4.0 |
| SC(B)13-400 | 400 | 705 | 3,590 | 3,850 | 0.85 | 4.0 |
| SC(B)13-630 | 630 | 965 | 5,290 | 5,660 | 0.72 | 4.0 |
| SC(B)13-630 | 630 | 935 | 5,365 | 5,760 | 0.72 | 6.0 |
| SC(B)13-1000 | 1,000 | 1,275 | 7,315 | 7,885 | 0.72 | 6.0 |
| SC(B)13-1600 | 1,600 | 1,765 | 10,555 | 11,320 | 0.72 | 6.0 |
| SC(B)13-2500 | 2,500 | 2,590 | 15,455 | 16,605 | 0.6 | 6.0 |

The SCB14 meets energy efficiency grade 2 under GB 20052-2020. It comes with smart temperature control and suits tenders that specify a grade.
| Rating | 30–2,500 kVA |
|---|---|
| HV / LV | 6 / 6.3 / 10 kV to 0.4 kV |
| Efficiency | Grade 2, GB 20052-2020 |
| Vector group | Yyn0 or Dyn11 |
| Model | kVA | No-load loss (W) | Load loss 120°C (W) | Load loss 145°C (W) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|---|---|
| SC14-100 | 100 | 290 | 1,415 | 1,520 | 1.28 | 4.0 |
| SC(B)14-250 | 250 | 515 | 2,485 | 2,665 | 0.94 | 4.0 |
| SC(B)14-400 | 400 | 705 | 3,590 | 3,850 | 0.85 | 4.0 |
| SC(B)14-630 | 630 | 965 | 5,290 | 5,660 | 0.72 | 4.0 |
| SC(B)14-630 | 630 | 935 | 5,365 | 5,760 | 0.72 | 6.0 |
| SC(B)14-1000 | 1,000 | 1,275 | 7,315 | 7,885 | 0.72 | 6.0 |
| SC(B)14-1600 | 1,600 | 1,765 | 10,555 | 11,320 | 0.72 | 6.0 |
| SC(B)14-2500 | 2,500 | 2,590 | 15,455 | 16,605 | 0.6 | 6.0 |

The SCB18 meets energy efficiency grade 1, the highest grade under GB 20052-2020. At 630 kVA its no-load loss is 775 W.
| Rating | 30–2,500 kVA |
|---|---|
| HV / LV | 6 / 6.3 / 10 kV to 0.4 kV |
| Efficiency | Grade 1, GB 20052-2020 |
| Vector group | Yyn0 or Dyn11 |
| Model | kVA | No-load loss (W) | Load loss 120°C (W) | Load loss 145°C (W) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|---|---|
| SC18-100 | 100 | 230 | 1,415 | 1,520 | 1.28 | 4.0 |
| SC(B)18-250 | 250 | 415 | 2,485 | 2,665 | 0.94 | 4.0 |
| SC(B)18-400 | 400 | 570 | 3,590 | 3,850 | 0.85 | 4.0 |
| SC(B)18-630 | 630 | 775 | 5,290 | 5,660 | 0.72 | 4.0 |
| SC(B)18-630 | 630 | 720 | 5,365 | 5,760 | 0.72 | 6.0 |
| SC(B)18-1000 | 1,000 | 1,020 | 7,315 | 7,885 | 0.72 | 6.0 |
| SC(B)18-1600 | 1,600 | 1,415 | 10,555 | 11,320 | 0.72 | 6.0 |
| SC(B)18-2500 | 2,500 | 2,080 | 15,455 | 16,605 | 0.6 | 6.0 |

The SC(B)H15 combines a three-limb amorphous alloy core with cast resin windings. At 630 kVA its no-load loss is 420 W, the lowest of our dry-type series.
| Rating | 30–2,500 kVA |
|---|---|
| HV / LV | 6 / 6.3 / 6.6 / 10 / 10.5 / 11 kV to 0.4 kV |
| Core | Three-limb amorphous alloy |
| Vector group | Dyn11 |
| Model | kVA | No-load loss (W) | Load loss 120°C (W) | Load loss 145°C (W) | No-load current (%) | Impedance (%) |
|---|---|---|---|---|---|---|
| SCBH15-100 | 100 | 130 | 1,570 | 1,690 | 1.2 | 4.0 |
| SCBH15-250 | 250 | 230 | 2,760 | 2,960 | 1.0 | 4.0 |
| SCBH15-400 | 400 | 310 | 3,990 | 4,280 | 0.8 | 4.0 |
| SCBH15-630 | 630 | 420 | 5,880 | 6,290 | 0.7 | 4.0 |
| SCBH15-630 | 630 | 410 | 5,960 | 6,400 | 0.7 | 6.0 |
| SCBH15-1000 | 1,000 | 550 | 8,130 | 8,760 | 0.6 | 6.0 |
| SCBH15-1600 | 1,600 | 760 | 11,730 | 12,580 | 0.6 | 6.0 |
| SCBH15-2500 | 2,500 | 1,200 | 17,170 | 18,450 | 0.5 | 6.0 |

The SG(B)13 has open, vacuum-pressure-impregnated windings that are not cast in resin. Class H (180°C) insulation lets it run hot and recover well from overloads, and fan cooling (AF) raises its capacity further.
| Rating | 30–2,500 kVA |
|---|---|
| Insulation | Class H (180°C) |
| Cooling | AN / AF |
| Loss groups | Group A and Group B |
| Model | kVA | Group A no-load (W) | Group A load 100/120/145°C (W) | Group B no-load (W) | Group B load 100/120/145°C (W) | Impedance (%) |
|---|---|---|---|---|---|---|
| SG(B)13-100 | 100 | 400 | 1480 / 1570 / 1690 | 360 | 1600 / 1690 / 1830 | 4.0 |
| SG(B)13-250 | 250 | 720 | 2590 / 2760 / 2960 | 660 | 2880 / 3070 / 3300 | 4.0 |
| SG(B)13-400 | 400 | 980 | 3750 / 3990 / 4280 | 890 | 4100 / 4350 / 4640 | 4.0 |
| SG(B)13-630 | 630 | 1,340 | 5530 / 5880 / 6290 | 1,200 | 5810 / 6140 / 6560 | 4.0 |
| SG(B)13-630 | 630 | 1,300 | 5610 / 5960 / 6400 | 1,160 | 5950 / 6330 / 6800 | 6.0 |
| SG(B)13-1000 | 1,000 | 1,770 | 7650 / 8130 / 8760 | 1,560 | 8250 / 8730 / 9420 | 6.0 |
| SG(B)13-1600 | 1,600 | 2,450 | 11050 / 11730 / 12580 | 2,400 | 11990 / 12770 / 13650 | 6.0 |
| SG(B)13-2500 | 2,500 | 3,600 | 16150 / 17170 / 18450 | 3,150 | 17380 / 18420 / 19720 | 6.0 |
| SG(B)13-1600 | 1,600 | 2,450 | 12280 / 12960 / 13900 | 2,400 | 12930 / 13720 / 14690 | 8.0 |
| SG(B)13-2500 | 2,500 | 3,600 | 17760 / 18890 / 20290 | 3,150 | 18700 / 19840 / 21330 | 8.0 |
| Voltage class (kV) | Highest voltage (kV rms) | Power-frequency withstand, 1 min (kV rms) | Lightning impulse, full wave (kV peak) |
|---|---|---|---|
| 0.4 | 0.46 | 5 | — |
| 10 | 12 | 35 | 75 (chopped wave 85) |
| 20 | 24 | 50 | 125 |
| 35 | 42 | 70 | 170 |
Designed and tested to GB 1094.11 and IEC 60076-11. Every unit gets routine tests before shipment, including a partial discharge measurement, and ships with its test report. Type tests and witness testing are available on request. Enclosures (IP20 to IP23), fans, temperature controllers and other voltage ratios are built to your specification.
Jiangsu Tianhua Transformer Co., Ltd. is a manufacturer, not a trading company. Every series on this page is designed, wound, assembled and tested in our plant in Xuzhou, Jiangsu, China. You talk directly to our engineers, and every unit ships with its routine test report.
They are cast resin dry-type transformers with different loss levels. At 630 kVA, no-load loss is 1,350 W for SC(B)10, 965 W for SC(B)13 and 775 W for SCB18. SCB18 meets energy efficiency grade 1 under GB 20052-2020.
S means three-phase, C means cast resin, and B means the low-voltage winding is made of copper or aluminium foil rather than wire. The number is the performance level.
Cast resin (SC(B) series) is best for humid or dusty indoor sites. Open-wound VPI (SG(B)13, class H) handles higher temperatures and frequent overloads.
Yes. We supply protective enclosures, cooling fans and temperature controllers to your specification.
Tell us the kVA, voltage and standard. We reply with a datasheet and price within 24 hours.