Factory-direct transformer manufacturer · Xuzhou, China

IEC 60076 · IEEE C57.12 · 50 Hz and 60 Hz designs

SC(B)10 Cast Resin Dry-Type Transformer, 10kV and 35kV, 30–2,500 kVA

SC(B)10 Cast Resin Dry-Type Transformer, 10kV and 35kV, 30–2,500 kVA

Specifications

Quick answer

The SC(B)10 is Tianhua’s epoxy cast resin dry-type transformer in two voltage classes: a 10 kV series from 30 to 2,500 kVA and a 35 kV series (35–38.5 kV) from 50 to 2,500 kVA. It is energy saving, maintenance-free, fire resistant and pollution-free.

SeriesSC(B)10, three-phase epoxy cast resin
Rating10 kV: 30–2,500 kVA; 35 kV: 50–2,500 kVA
HV6 / 6.3 / 10 kV or 35–38.5 kV
LV0.4 kV (10 kV series); 3.5–11 kV (35 kV series)
Impedance4%, 6% or 8% (10 kV); 6% (35 kV)
Insulation35 kV class: 70 kV power frequency, 170 kV lightning impulse
ManufacturerJiangsu Tianhua Transformer Co., Ltd., Xuzhou, China

Get a quote in 24 hoursEmail our engineers

Key advantages · Type designation · SC(B)10 10kV series · How to order · FAQ

Key advantages

  • Energy saving and maintenance-free
  • Better fire performance than oil: no oil, no pollution
  • Easy installation close to the load
  • Complete drawings and documentation; advanced, proven production
  • Performance confirmed by users in long-term operation

Type designation: SC(B)10-□/□

  • S: three-phase
  • C: epoxy resin cast
  • B: low-voltage foil winding
  • 10: performance level code
  • □: rated capacity (kVA) / voltage class (kV)

SC(B)10 10kV series

ModelkVANo-load loss (W)Load loss 120°C (W)Load loss 145°C (W)No-load current (%)Impedance (%)
SC10-30301907107602.04.0
SC10-50502701,0001,0702.04.0
SC10-80803701,3801,4801.54.0
SC10-1001004001,5701,6901.54.0
SC10-1251254701,8501,9801.34.0
SCB10-1601605502,1302,2801.34.0
SCB10-2002006302,5302,7101.14.0
SCB10-2502507202,7602,9601.14.0
SCB10-3153158803,4703,7301.04.0
SCB10-4004009803,9904,2801.04.0
SCB10-5005001,1604,8805,2301.04.0
SCB10-6306301,3505,8806,2900.854.0
SCB10-6306301,3005,9606,4000.856.0
SCB10-8008001,5206,9607,4600.856.0
SCB10-10001,0001,7708,1308,7600.856.0
SCB10-12501,2502,0909,69010,3000.856.0
SCB10-16001,6002,45011,70012,5000.856.0
SCB10-20002,0003,05014,40015,5000.76.0
SCB10-25002,5003,60017,10018,4000.76.0
SCB10-16001,6002,45012,90013,9000.858.0
SCB10-20002,0003,05015,90017,1000.78.0
SCB10-25002,5003,60018,80020,2000.78.0

1,600–2,500 kVA is also available with 8% impedance (last three rows).

SC10 35kV series (off-circuit tap changer)

ModelkVAVector groupLV (kV)No-load loss (W)Load loss 120°C (W)Load loss 145°C (W)No-load current (%)Impedance (%)
SC10-5050Dyn11 / Yd11 / Yyn03.5–114501,4201,5202.36.0
SC10-100100Dyn11 / Yd11 / Yyn03.5–116302,0902,2302.06.0
SC10-160160Dyn11 / Yd11 / Yyn03.5–117902,8103,0001.56.0
SC10-200200Dyn11 / Yd11 / Yyn03.5–118803,3203,5501.56.0
SC10-250250Dyn11 / Yd11 / Yyn03.5–119903,8004,0601.36.0
SC10-315315Dyn11 / Yd11 / Yyn03.5–111,1704,5104,8201.36.0
SC10-400400Dyn11 / Yd11 / Yyn03.5–111,3705,4105,7901.16.0
SC10-500500Dyn11 / Yd11 / Yyn03.5–111,6206,6507,1101.16.0
SC10-630630Dyn11 / Yd11 / Yyn03.5–111,8607,6908,2301.06.0
SC10-800800Dyn11 / Yd11 / Yyn03.5–112,1609,1209,7601.06.0
SC10-10001,000Dyn11 / Yd11 / YNd113.5–112,43010,40011,1000.756.0
SC10-12501,250Dyn11 / Yd11 / YNd116–112,83012,70013,6000.756.0
SC10-16001,600Dyn11 / Yd11 / YNd116–113,24015,40016,5000.756.0
SC10-20002,000Dyn11 / Yd11 / YNd116–113,82018,20019,5000.756.0
SC10-25002,500Dyn11 / Yd11 / YNd116–114,45021,80023,3000.756.0

LV options: 3.5 / 6 / 6.3 / 10 / 10.5 / 11 kV up to 1,000 kVA; 6 / 6.3 / 10.5 / 11 kV from 1,250 kVA.

Insulation levels

Voltage class (kV)Highest voltage (kV rms)Power-frequency withstand, 1 min (kV rms)Lightning impulse, full wave (kV peak)
0.40.465—
10123575 (chopped wave 85)
202450125
354270170

Data from the Tianhua product catalogue. Capacity, voltage ratio, vector group, impedance, losses and dimensions can be designed to your specification.

Applications

  • Industrial plants and mines
  • 35 kV step-down and step-up in renewable plants
  • Buildings, tunnels and transport hubs

Standards and testing

Designed and tested to GB 1094.11 and IEC 60076-11. Routine tests on every unit before shipment, including partial discharge measurement, with the test report supplied. Type tests and witness testing on request.

How to order

Send us

  • rated power and quantity
  • primary and secondary voltage, vector group and tapping range
  • standard (IEC, IEEE / ANSI, GB or your utility specification) and frequency
  • any loss limits or efficiency rule
  • site conditions: altitude, ambient temperature, indoor or outdoor, corrosion
  • destination port and preferred Incoterm

What happens next

  • datasheet and price within 24 hours
  • drawings for your approval
  • production after drawing approval and advance payment, on the date confirmed in the quotation
  • routine tests and test report; witness test on request
  • export packing and shipping

Shipping policy · Terms and conditions

Who makes this transformer

Transformer workshop at the Tianhua factory in Xuzhou, China

Jiangsu Tianhua Transformer Co., Ltd. designs, builds and tests this transformer in its own 107,000 m² plant in Xuzhou, Jiangsu, China. Founded in 2013, Tianhua is a manufacturer, not a trading company: you deal directly with our engineers, and inspectors are welcome to witness the factory acceptance test.

  • 500+ employees, including 7 senior engineers
  • ISO 9001 quality system; IEC, IEEE / ANSI and GB designs
  • Exported to more than 30 countries and regions

About Tianhua · Factory and testing · Certificates · Projects

Frequently asked questions

Do you make 35kV dry-type transformers?

Yes. The SC10 35 kV series covers 50–2,500 kVA, HV 35–38.5 kV, LV 3.5–11 kV, with 6% impedance.

What are the insulation levels of a 35kV dry transformer?

Highest voltage 42 kV, power-frequency withstand 70 kV for 1 minute and lightning impulse 170 kV.

What is the no-load loss of an SCB10-1000 (10kV)?

1,770 W, with load loss 8,130 W at 120°C and 6% impedance.

How long does the SC(B)10 dry-type transformer take to make?

Production starts after drawing approval and advance payment. The delivery date depends on rating and quantity and is confirmed in the quotation.

Can the SC(B)10 dry-type transformer be built to my specification?

Yes. Rating, voltage ratio, vector group, impedance, losses, accessories and dimensions can be designed to your specification and standard.

How is the SC(B)10 dry-type transformer shipped?

In a container, in a closed wooden case that protects it from moisture and dust. The enclosure is fitted or packed separately.

What warranty does Tianhua give?

The warranty is 1 to 2 years depending on the product and size, confirmed in the quotation and sales contract.

Get a quotation for the SC(B)10 dry-type transformer

Send capacity, voltage ratio, standard, quantity and destination. Our engineers reply with a datasheet and price within 24 hours.

Email sale@thatransformer.comWhatsAppCall Ivy Xiao

Data from the Tianhua product catalogue. Written by the Tianhua Transformer engineering team, Xuzhou, China. Last updated November 2026.

Routine test report

Every unit tested before shipment

Factory-direct

Built in our Xuzhou plant

Built to your spec

IEC, IEEE/ANSI or GB

Quote in 24 hours

Datasheet and price from our engineers

More from our factory

Power, distribution, dry-type and substation equipment, all designed, built and tested in our Xuzhou plant.

View all products
Need several units or a full project?

Send your single-line diagram or bill of quantities. Our engineers reply with a datasheet and price within 24 hours.