The SC(B)12 is an epoxy cast resin dry-type transformer for 6–10 kV networks, rated 30–2,500 kVA. Its no-load loss is over 20% lower than SC(B)11 and noise 10–15 dB below JB/T 10088-2004, with partial discharge controlled to 5 pC. Made by Jiangsu Tianhua Transformer Co., Ltd. in Xuzhou, China.
Series
SC(B)12, three-phase epoxy cast resin
Rating
30–2,500 kVA
HV / LV
6 / 6.3 / 10 kV to 0.4 kV
Vector group
Yyn0 or Dyn11
Partial discharge
≤5 pC
Certification
National PCCC energy-saving certified product
Manufacturer
Jiangsu Tianhua Transformer Co., Ltd., Xuzhou, China
High mechanical strength for sudden short circuits
Maintenance-free and economical to run
Type designation: SC(B)12-□/□
S: three-phase
C: epoxy resin cast
B: low-voltage foil winding
12: performance level code
□: rated capacity (kVA) / voltage class (kV)
SC(B)12 10kV rating table
Model
kVA
No-load loss (W)
Load loss 120°C (W)
Load loss 145°C (W)
No-load current (%)
Impedance (%)
SC12-30
30
150
710
760
1.7
4.0
SC12-50
50
215
1,000
1,070
1.7
4.0
SC12-80
80
295
1,380
1,480
1.28
4.0
SC12-100
100
320
1,570
1,690
1.28
4.0
SC12-125
125
375
1,850
1,980
1.11
4.0
SC(B)12-160
160
430
2,130
2,280
1.11
4.0
SC(B)12-200
200
495
2,530
2,710
0.94
4.0
SC(B)12-250
250
575
2,760
2,960
0.94
4.0
SC(B)12-315
315
705
3,470
3,730
0.85
4.0
SC(B)12-400
400
785
3,990
4,280
0.85
4.0
SC(B)12-500
500
930
4,880
5,230
0.85
4.0
SC(B)12-630
630
1,070
5,880
6,290
0.72
4.0
SC(B)12-630
630
1,040
5,960
6,400
0.72
6.0
SC(B)12-800
800
1,210
6,960
7,460
0.72
6.0
SC(B)12-1000
1,000
1,410
8,130
8,760
0.72
6.0
SC(B)12-1250
1,250
1,670
9,690
10,370
0.72
6.0
SC(B)12-1600
1,600
1,960
11,730
12,580
0.72
6.0
SC(B)12-2000
2,000
2,440
14,450
15,560
0.6
6.0
SC(B)12-2500
2,500
2,880
17,170
18,450
0.6
6.0
630 kVA is listed with 4% and 6% impedance.
Data from the Tianhua product catalogue. Capacity, voltage ratio, vector group, impedance, losses and dimensions can be designed to your specification.
Applications
Power stations and plants
Hospitals, airports and tunnels
Chemical plants and nuclear power plants
Standards and testing
Designed and tested to GB 1094.11 and IEC 60076-11. Routine tests on every unit before shipment, including partial discharge measurement, with the test report supplied. Type tests and witness testing on request.
How to order
Send us
rated power and quantity
primary and secondary voltage, vector group and tapping range
standard (IEC, IEEE / ANSI, GB or your utility specification) and frequency
any loss limits or efficiency rule
site conditions: altitude, ambient temperature, indoor or outdoor, corrosion
destination port and preferred Incoterm
What happens next
datasheet and price within 24 hours
drawings for your approval
production after drawing approval and advance payment, on the date confirmed in the quotation
routine tests and test report; witness test on request
Jiangsu Tianhua Transformer Co., Ltd. designs, builds and tests this transformer in its own 107,000 m² plant in Xuzhou, Jiangsu, China. Founded in 2013, Tianhua is a manufacturer, not a trading company: you deal directly with our engineers, and inspectors are welcome to witness the factory acceptance test.
500+ employees, including 7 senior engineers
ISO 9001 quality system; IEC, IEEE / ANSI and GB designs