The SG(B)13 is a non-encapsulated (open-wound) dry-type transformer with class H (180°C) insulation and whole-unit vacuum impregnation. It runs at 120% load continuously and 140% for 3 hours without forced cooling, and gives almost no smoke at high temperature. Ratings 30–2,500 kVA. Made by Jiangsu Tianhua Transformer Co., Ltd. in Xuzhou, China.
Series
SG(B)13, three-phase, non-encapsulated windings
Rating
30–2,500 kVA
Insulation
Class H (180°C)
Cooling
AN, air self-cooling
Overload
120% continuous; 140% for 3 hours, no forced cooling
Impedance
4%, 6% or 8%
Fire behaviour
Flame-retardant, non-toxic, self-extinguishing
Manufacturer
Jiangsu Tianhua Transformer Co., Ltd., Xuzhou, China
Continuous HV winding and LV foil winding, whole-unit vacuum impregnation and curing
High-strength ceramic supports for strong short-circuit withstand
Almost no smoke under high-temperature open flame
Thin, uniform insulation for excellent heat dissipation
Strong heat-shock resistance and high overload capacity
Full load immediately after storage at ±50°C
Type designation: SG(B)13-□/□
S: three-phase
G: dry type, air self-cooling
B: low-voltage foil winding
13: performance level code
□: rated capacity (kVA) / voltage class (kV)
SG(B)13 rating table, Group A and Group B losses
Model
kVA
Group A no-load (W)
Group A load 100/120/145°C (W)
Group B no-load (W)
Group B load 100/120/145°C (W)
Impedance (%)
SG(B)13-30
30
190
670 / 710 / 760
180
700 / 740 / 790
4.0
SG(B)13-50
50
270
940 / 1000 / 1070
250
1010 / 1060 / 1140
4.0
SG(B)13-80
80
370
1290 / 1380 / 1480
330
1370 / 1470 / 1570
4.0
SG(B)13-100
100
400
1480 / 1570 / 1690
360
1600 / 1690 / 1830
4.0
SG(B)13-125
125
470
1740 / 1850 / 1980
420
1870 / 1980 / 2120
4.0
SG(B)13-160
160
540
2000 / 2130 / 2280
490
2120 / 2320 / 2480
4.0
SG(B)13-200
200
620
2370 / 2530 / 2710
580
2550 / 2690 / 2880
4.0
SG(B)13-250
250
720
2590 / 2760 / 2960
660
2880 / 3070 / 3300
4.0
SG(B)13-315
315
880
3270 / 3470 / 3730
780
3450 / 3690 / 3970
4.0
SG(B)13-400
400
980
3750 / 3990 / 4280
890
4100 / 4350 / 4640
4.0
SG(B)13-500
500
1,160
4590 / 4880 / 5230
1,040
4870 / 5160 / 5530
4.0
SG(B)13-630
630
1,340
5530 / 5880 / 6290
1,200
5810 / 6140 / 6560
4.0
SG(B)13-630
630
1,300
5610 / 5960 / 6400
1,160
5950 / 6330 / 6800
6.0
SG(B)13-800
800
1,520
6550 / 6960 / 7460
1,370
6960 / 7380 / 7900
6.0
SG(B)13-1000
1,000
1,770
7650 / 8130 / 8760
1,560
8250 / 8730 / 9420
6.0
SG(B)13-1250
1,250
2,090
9100 / 9690 / 10370
1,810
9830 / 10390 / 11140
6.0
SG(B)13-1600
1,600
2,450
11050 / 11730 / 12580
2,400
11990 / 12770 / 13650
6.0
SG(B)13-2000
2,000
3,050
13600 / 14450 / 15560
2,700
14450 / 15300 / 16540
6.0
SG(B)13-2500
2,500
3,600
16150 / 17170 / 18450
3,150
17380 / 18420 / 19720
6.0
SG(B)13-1600
1,600
2,450
12280 / 12960 / 13900
2,400
12930 / 13720 / 14690
8.0
SG(B)13-2000
2,000
3,050
15020 / 15960 / 17110
2,700
15770 / 16720 / 18060
8.0
SG(B)13-2500
2,500
3,600
17760 / 18890 / 20290
3,150
18700 / 19840 / 21330
8.0
Load loss shown at insulation reference temperatures B (100°C) / F (120°C) / H (145°C). The last three rows are the 8% impedance versions.
Data from the Tianhua product catalogue. Capacity, voltage ratio, vector group, impedance, losses and dimensions can be designed to your specification.
Applications
Industrial plants with frequent overloads
Rectifier and drive supplies
High-rise buildings and public facilities needing low smoke
Standards and testing
Designed and tested to GB 1094.11 and IEC 60076-11. Routine tests on every unit before shipment, including partial discharge measurement, with the test report supplied. Type tests and witness testing on request.
How to order
Send us
rated power and quantity
primary and secondary voltage, vector group and tapping range
standard (IEC, IEEE / ANSI, GB or your utility specification) and frequency
any loss limits or efficiency rule
site conditions: altitude, ambient temperature, indoor or outdoor, corrosion
destination port and preferred Incoterm
What happens next
datasheet and price within 24 hours
drawings for your approval
production after drawing approval and advance payment, on the date confirmed in the quotation
routine tests and test report; witness test on request
Jiangsu Tianhua Transformer Co., Ltd. designs, builds and tests this transformer in its own 107,000 m² plant in Xuzhou, Jiangsu, China. Founded in 2013, Tianhua is a manufacturer, not a trading company: you deal directly with our engineers, and inspectors are welcome to witness the factory acceptance test.
500+ employees, including 7 senior engineers
ISO 9001 quality system; IEC, IEEE / ANSI and GB designs
What is the difference between SG(B)13 and cast resin transformers?
SG(B)13 windings are vacuum impregnated, not encapsulated in epoxy. They use class H insulation, dissipate heat better and tolerate 120% continuous overload.
What overload can SG(B)13 carry?
120% of rated load continuously and 140% for 3 hours, without forced-air cooling.
What do Group A and Group B mean?
They are two loss levels listed in the catalogue. Group B has lower no-load loss, for example 1,560 W against 1,770 W at 1000 kVA.
How long does the SG(B)13 VPI dry-type transformer take to make?
Production starts after drawing approval and advance payment. The delivery date depends on rating and quantity and is confirmed in the quotation.
Can the SG(B)13 VPI dry-type transformer be built to my specification?
Yes. Rating, voltage ratio, vector group, impedance, losses, accessories and dimensions can be designed to your specification and standard.
How is the SG(B)13 VPI dry-type transformer shipped?
In a container, in a closed wooden case that protects it from moisture and dust. The enclosure is fitted or packed separately.
What warranty does Tianhua give?
The warranty is 1 to 2 years depending on the product and size, confirmed in the quotation and sales contract.